Features and Benefits
The DTS-60A(F) is a fully automatic liquid dielectric test set, typically used for testing the voltage breakdown level of insulating oils. The most common world standards are pre-programmed into the controls. Just hit the start button and the test is performed. Custom test sequences can also be programmed. Test results stored internally can be downloaded to a computer or printed using the onboard thermal printer.
These lightweight, rugged units have been designed for both field and laboratory use. Their HV transformer section is a leak-proof conventional steel tank with a gasket-bolted lid. The enclosures are made of thick aluminium. These instruments withstand the rigours of frequent transport and substation use.
Specifications
Input:
120 V, 60 Hz, 7 A
(F) 230 V, 50/60 Hz, 4 A
Output:
0 – 60 kV AC, 800 VA resistive load
Controls:
10 pre-programmed test sequences
User programmable test routines</>128 x 64 dot matrix crystal display
Intuitive, easy to use controls English, German, Spanish, French, Greek
Thermal printer
Oil Test Cells:
TCD-3 for ASTM D877, TCD-5 for ASTM D1816, TCD-12 for IEC 156
Size & Weight:
(W x D x H)
15 x 14 x 11.5 in., 65 lb.
381 x 356 x 292 mm, 29 kg