Features and Benefits
The PFT-302CE is a CE Marked AC hipot test set from our popular PFT Series. These hipots provide continuously adjustable AC voltage used for a pass/fail, AC over-voltage withstand test on high voltage apparatus, like switchgear, circuit breakers, reclosers, vacuum bottles, hot sticks, bus duct, and any other apparatus needing an AC test voltage. The PFT Series offers the most field portable, affordable, and easiest to operate AC hipots at this voltage and power. The PFT-302CE is equipped with high end features such as digital meters, an adjustable overload, keyed main power switch, 20ft shielded output cable and a guard circuit for precise leakage current measurement. For benchtop requirements see the ABT Series. Testing loads that require higher power, see our ALT, FPA, HPA and PAR lines of AC dielectric test sets.
Convenient one-piece field portable design
Digital voltmeter and current meter
CE Marked
Adjustable overload, 10 – 110% of rated output current
Keyed main power switch
Guard/Ground circuit for accurate leakage current measurement
20 ft x-ray shielded output cable and shielded return cable
Zero Start and External safety Interlock provisions
Specifications
Input:
230 V, 50/60 Hz, 15 A
Output:
0-30 kV AC, 2 kVA resistive load
2 kVA capacitive load, up to 67 mA current
Duty:
2kVA: 1 hour ON, 1 hour OFF
1kVA: continuous
Distortion:
Less than 5%
Meter Accuracy:
1%
Voltmeter:
3.5 digit LED, scaled 0-30 kV AC, ±1% F.S.
Current Meter:
3.5 digit LED, scaled 0-67 mA AC, ±1% F.S.
Size & Weight:
(W x D x H)
23 x 11.5 x 15.5 in., 77 lb
584 x 292 x 394 mm, 35 kg
Output Termination:
20 ft. (6 m) output cable with alligator clamp
Scope Of Supply:
20ft green/yellow ground lead, 20ft shielded return cable, external interlock plug, main power key, operations manual, calibration certificate
Optional Accessories
Hand & Foot Safety Switches
PN 90-410
PN 90-405
Safety Ground Sticks
14 inch PN 88-150
10 inch PN 88-113