Features and Benefits
The VLF-12011CMF provides a 120 kV AC peak output voltage, suitable for VLF hipot testing 69 kV cable and as a voltage source for partial discharge and tan delta testing of 115 kV cable. It offers a complete control package including cable burn mode, which reduces fault arc over voltage events so that conventional thumpers can be deployed for fault locating. This model comes in a one-piece package with cable reels.
Specifications
Input:
230 V, 50/60 Hz, 30 A peak, 25 A average
Output:
0-120 kV AC peak, 0.1/0.05/0.02 Hz sinusoidal
Duty:
Continuous
Load Rating:
0.55 µF @ 0.1 Hz
1.1 µF @ 0.05 Hz
2.75 µF @ 0.02 Hz
5.5 µF @ 0.01 Hz
Voltmeter:
0 – 120 kV ACpeak
Charging Current Meter:
0 – 100 mA peak
Load Capacitance Meter:
0 – 6 µF
Test Duration Timer:
Programmable
Output Termination:
Shielded EPR output cable – 100 ft. (30 m)
Ground cable – 100 ft. (30 m)
Size & Weight:
(W x D x H)
Controls:
17 x 11 x 9.5 in., 20 lb.
432 x 280 x 241 mm, 9 kg
Regulator:
20 x 14 x 27 in., 160 lb.
508 x 356 x 686 mm, 73 kg
HV Tank:
26 x 20 x 22 in., 390 lb.
660 x 508 x 559 mm, 177 kg