Features and Benefits
VLF-65CMF is a higher power model designed to test long cables rated up to 35 kV. It includes a complete controls package with cable burn mode, used to reduce fault arc over voltages so that conventional thumpers can be deployed. Its cable reels provide 100’ (30 m) of HV and ground cable.
Specifications
Input:
230 V, 50/60 Hz, 30 A peak, 25 A average
Output:
0 – 65 kV AC peak, 0.1/0.05/0.02/0.01 Hz sinusoidal
Duty:
Continuous
Load Rating:
2.2 µF @ 0.1 Hz
4.4 µF @ 0.05 Hz
11.0 µF @ 0.02 Hz
22.0 µF @ 0.01 Hz
Voltmeter:
0 – 75 kV AC peak
Charging Current Meter:
0 – 200 mA peak
Load Capacitance Meter:
0 – 6 µF
Test Duration Timer:
Programmable
Output Termination:
Shielded EPR output cable – 100 ft. (30 m)
Ground cable – 100 ft. (30 m)
Size & Weight:
(W x D x H)
Controls:
17 x 11 x 9.5 in., 20 lb.
432 x 280 x 241 mm, 9 kg
Regulator:
20 x 14 x 27 in., 160 lb.
508 w x 356 x 686 mm, 73 kg
HV Tank:
15 x 18 x 22 in, 215 lb.
381 x 457 x 559 mm, 98 kg